This article covers what the designation actually means, how to select the right size and colour, and the practical considerations around spool sizes and stocking.
What THHN actually stands for
The letters describe the insulation, not the conductor.
T for thermoplastic insulation
HH for high heat resistance, rated to ninety degrees Celsius in dry locations
N for a nylon outer jacket
That nylon jacket is the reason THHN pulls as easily as it does. It resists abrasion and reduces friction through conduit runs and around bends.
THHN, THWN and why most wire is both
You will see wire marked THHN/THWN-2 far more often than THHN alone, and there is a reason for that.
THHN is rated ninety degrees Celsius in dry locations only
THWN is rated for wet locations
THWN-2 is rated ninety degrees Celsius in both wet and dry locations
Manufacturers found it simpler to produce one conductor meeting all of these than to run separate product lines. The result is that most building wire sold today carries dual or triple ratings printed on the jacket.
This matters practically. Underground conduit, outdoor runs and any conduit that can accumulate condensation count as wet locations. A conductor rated for dry locations only is not appropriate there. Check the printing on the jacket rather than assuming.
Sizing the conductor
Conductor sizing is driven by ampacity, and ampacity depends on more than just wire gauge.
The factors that matter:
Conductor size, in American Wire Gauge
Insulation temperature rating
Ambient temperature at the installation location
Number of current carrying conductors in the same raceway
Termination temperature ratings on the equipment at each end
That last point causes regular confusion. A conductor may be rated for ninety degrees Celsius, but if the breaker and lug terminations are rated seventy five degrees, the lower rating governs. The ninety degree rating is used for derating calculations, not for determining final ampacity at the terminations.
Common sizes and typical applications:
Fourteen gauge for fifteen amp lighting and general purpose circuits
Twelve gauge for twenty amp circuits, including most receptacle circuits
Ten gauge for thirty amp circuits, water heaters and smaller equipment
Eight gauge for forty amp circuits
Six gauge for fifty to sixty amp circuits, ranges and subpanels
These are starting points. Voltage drop on long runs frequently pushes the required size up a step or two beyond what ampacity alone would suggest. On runs over a hundred feet it is worth calculating rather than assuming.
Colour conventions
Colour coding is partly code requirement and partly convention, and getting it wrong creates problems for whoever works on the system next.
Required:
White or grey for grounded neutral conductors
Green, green with yellow stripe, or bare for equipment grounding conductors
Convention for ungrounded conductors, widely followed:
Black, red and blue for 120/208 volt systems
Brown, orange and yellow for 277/480 volt systems
Orange carries a specific meaning in some systems as the high leg on a delta configuration, so it is worth being deliberate rather than grabbing whatever is on the shelf.
Keeping consistent colour discipline across a job is not just tidiness. It makes troubleshooting faster and reduces the chance of a dangerous assumption by the next person in the panel.
Conduit fill
Overfilling conduit is one of the more common inspection failures and it is entirely avoidable.
The principles:
One conductor in a conduit is limited to fifty three percent of the internal area
Two conductors are limited to thirty one percent
Three or more are limited to forty percent
Those percentages account for heat dissipation and for the practical reality of pulling conductors without damaging insulation. The fill tables in the code handle the arithmetic, and most manufacturers publish quick reference charts.
Where derating also applies, running more than three current carrying conductors in a raceway reduces the ampacity of each. Pushing a conduit to the fill limit and then discovering the derated ampacity no longer covers the load is a frustrating way to learn this.
Spool sizes and stocking
Building wire is sold on spools of various lengths, and choosing the right one affects both cost and waste.
Five hundred foot spools suit most residential and light commercial work, and the common branch circuit sizes
Twenty five hundred foot spools suit larger gauges and higher volume work, particularly feeders and service conductors
The economics favour the larger spool per foot, but only if the wire gets used. A partially used twenty five hundred foot spool of an unusual colour sitting in the van for two years is not a saving.
For contractors stocking a van or a shop, a practical approach:
Twelve and fourteen gauge in the common colours on five hundred foot spools, since these move fastest
Larger gauges ordered per job unless you run consistent volume
Green and white in proportion to the ungrounded conductors you actually use
Practical handling
A few things that save time and avoid damage:
Pulling lubricant on long runs or runs with multiple bends, even with the nylon jacket
Avoiding sharp bends during the pull, which can damage insulation without visible evidence
Keeping spools out of direct sunlight for extended periods, since UV exposure degrades the jacket over time
Checking the printed markings on the jacket rather than relying on colour alone to identify a conductor type
For property owners
If you are having electrical work done, you will not be specifying wire. What is worth knowing is that conductor sizing is not arbitrary and that undersized wire on a circuit is a genuine safety issue rather than a technicality.
If an electrician proposes upsizing conductors on a long run, that is usually a voltage drop consideration rather than an upsell. Voltage drop causes equipment to underperform and motors to run hot, and the fix is larger wire.